Information

Mitsubishi HMI GOT GT Designer Part 6 - Numerical Display (Filipino) with English Subtitle

Basic shortcuts

Ctrl + SSave subtitles
Ctrl + click
Double click
Edit highlighted caption
TabEdit next caption
Shift + TabEdit previous caption
EscLeave edit mode
Ctrl + SpacePlay / pause video
Ctrl + HomePlay selected caption
Ctrl + EnterSplit caption at cursor position
at current time

Advanced shortcuts

Ctrl + InsertAdd new caption
Ctrl + DeleteDelete selected caption
Ctrl + IEdit currently played segment
Shift + EnterNew line when editing
Ctrl + LeftPlay from -1s
Ctrl + RightPlay from +1s
Alt + LeftShift caption start time -0.1s
Alt + RightShift caption start time +0.1s
Alt + DownShift caption end time -0.1s
Alt + UpShift caption end time +0.1s

Annotation shortcuts

Ctrl + 1Hesitation
Ctrl + 2Speaker noise
Ctrl + 3Background noise
Ctrl + 4Unknown word
Ctrl + 5Wrong segment
Ctrl + 6Crosstalk segment
You are in the read-only mode. Close
00:03.9
00:05.7
Welcome to this tutorial for Mitsubishi Graphic Operation Terminal
00:06.7
00:10.8
The Graphic Operation Terminal is the product name of
00:10.9
00:13.6
Mitsubishi HMI's.
00:14.7
00:18.4
Today's topic is about Numerical Display.
00:19.5
00:24.9
The numerical display allows the data saved in the PLC CPU and
00:25.0
00:42.5
other devices such as VFD's to be displayed as numeric values on GOT.
00:44.2
00:54.7
Examples of data that can be displayed on the are motor speed through vfd,
00:58.7
01:09.3
temperature, pressure or liquid level coming from process instruments,
01:09.4
01:16.3
current, timer values or counter values.
01:19.0
01:25.0
To add a numerical display to the screen editor
01:25.1
01:30.2
click the numerical input/display icon directly
01:30.3
01:35.8
and click on the screen editor on the desired location.
01:35.9
01:40.2
When double clicked, numerical display or
01:40.3
01:42.2
numerical input can be selected.
01:45.0
01:51.0
By clicking on the dropdown button on the numerical input/display icon
01:51.1
01:55.2
the numerical display or numerical input can be selected directly.
02:01.0
02:14.3
In the Basic Settings, Device Style tab add the address of the device
02:14.4
02:19.2
where the data to be displayed comes from.
02:19.3
02:29.0
Numerical data can be monitored from data registers, timer values,
02:30.5
02:37.5
timer set values, counter running values, counter set values,
02:40.0
02:46.0
X input, example from thumbwheel switches,
02:46.5
02:53.2
Y output, example outputs to seven segments digital displays,
02:53.5
02:59.0
or M auxiliary relays.
02:59.5
03:08.0
On our first example we will display the value of data register D11.
03:11.5
03:28.0
Supposing we want to monitor the value that is transferred to D11,
03:37.0
03:48.0
that is an example of numerical display.
03:55.6
04:02.4
In the Data Type, we have choices from Signed BIN16 ,
04:02.5
04:16.0
meaning 16 bit integers with negative and positive values,
04:16.1
04:27.5
Unsigned BIN16 are positive 16 bit integers,
04:37.8
04:45.0
The same as Signed BIN32 and Unsigned BIN32.
04:45.4
04:49.5
The only difference is the length of data which is 32 bits.
04:50.0
04:55.9
BCD16 is a 16 Bit Binary Coded Decimal,
04:56.0
05:00.6
while BCD32 is a 32 Bit Binary Coded Decimal.
05:02.0
05:05.5
Real numbers are floating point numbers
05:05.6
05:19.0
that have the ability to represent fractional portions of whole numbers.
05:30.0
05:37.0
Decimal is denary number or base 10 number that uses 10 digits from 0 to 9.
05:37.2
05:56.5
Hexadecimal is a base 16 number from 0 to 9 and continues from A to F.
05:57.6
06:04.8
Octal is a base 8 numbering system represented from 0 to 7.
06:04.9
06:11.5
Binary is a Base 2 numbering system that has a value of 0 or 1.
06:11.7
06:17.5
Real format is the same as in the Data Type which is a floating number.
06:23.0
06:35.9
Selecting this option will display the numerical values with asterisk.
06:43.0
06:48.9
This is useful when entering passwords.
06:52.9
07:05.8
Set the number of digits for the numeric value to be displayed.
07:07.4
07:28.2
Select this item for displaying zeros on the left to the numeric value.
08:18.2
08:33.5
Format string is set if we want to include characters with the device values.
08:33.6
08:39.7
Input "#" for the part where a numeric is displayed
08:44.5
08:58.5
then type the alphanumeric characters and symbols.
09:09.0
09:21.9
When Format String is used the Digit and Decimal point settings are disabled.
09:24.9
09:37.6
The "#" signs set with the format string setting are replaced by a device value when displayed.
09:49.0
09:58.0
Setting for Decimal Point will also be disabled when Signed or Unsigned Decimal is selected in the Format.
09:58.1
10:03.9
If Real is selected the Decimal Point setting will be enabled.
10:11.0
10:13.7
Decimal points can be adjusted
10:13.8
10:19.0
to display the device value of integer as a value with decimal point.
10:40.5
10:52.2
Shapes can be set as frames for numerical display.
11:29.1
11:44.6
Now we will make a numerical display for counter values.
11:47.0
11:49.6
In the Device setting select Counter and provide the address.
11:49.7
11:56.0
We will be monitoring the counter value.
12:06.2
12:08.6
Click the Display Case tab.
12:08.7
12:15.7
Here we can add conditions
12:15.8
12:20.6
to change the display according to the status of the monitored device.
12:44.9
13:05.1
For example, when the output Y0 is activated.
13:14.0
13:25.5
When Y0 is On, the display will blink. We will set to medium.
13:25.6
13:34.5
and set the numerical to red.
13:41.9
13:56.4
Extended Tab is for Security settings.
13:56.5
14:06.5
This will be discussed on another tutorial regarding security settings.
14:20.2
14:29.0
Trigger Tab sets conditions for displaying the object.
14:31.7
14:40.5
For example we select ON, we have to set the Trigger Device also.
14:40.6
14:48.6
If the trigger is satisfied,
14:48.7
14:59.9
the input display will monitor the current value of the device.
15:00.0
15:03.2
If the trigger is not satisfied, the value of the device will not be monitored.
15:03.7
15:09.9
For example we enter M0 as the trigger device.
15:17.0
15:40.0
If the Hold display is set, the display is hold
15:40.1
15:44.7
even when the display condition is no longer satisfied.
15:44.8
15:48.1
When the display condition is again satisfied
15:48.2
15:54.5
the current value of the monitored device will be displayed.
16:04.2
16:10.9
We will put a bit switch to increment the value of the counter.
16:18.8
16:26.0
Another bit switch to reset the counter.
16:27.4
16:40.6
Then a bit switch for the trigger device
16:47.1
16:53.1
Since the trigger switch is OFF, the input display is not shown.
16:55.5
16:59.2
When the trigger is switched On, the input display becomes visible.
17:23.0
17:29.4
The value of the counter will be incremented everytime the switch is pressed.
17:29.5
17:38.6
When the preset value is reached,
17:38.7
17:45.0
the counter contact will close
17:45.1
17:48.0
and the output Y0 will turn On.
17:49.5
17:52.4
The numerical display will then start blinking and turn into red.
17:55.5
18:02.5
That is because we have set a condition in the Display Case
18:02.6
18:10.0
that when Y0 turns On, the numerical display will change its color
18:10.1
18:11.4
into red and start blinking.
18:17.5
18:22.5
Once we turn off the trigger switch
18:22.6
18:26.5
the numerical display cannot be viewed.
18:45.0
18:53.3
With the Hold Display, the numerical display is still visible
18:53.4
19:04.1
but the value of the monitored device will be hold.
19:13.6
19:16.9
When we turn off the trigger switch,
19:17.0
19:22.0
even if the increment switch is pressed repeatedly
19:22.1
19:28.4
the value displayed is not updated.
19:28.5
19:31.0
Once the trigger switch is turned on,
19:31.1
19:41.3
the numerical display will show the current value of the monitored device.
19:41.4
19:50.9
That is the function of Trigger Device with Hold Display.
19:58.4
20:05.6
Next we will see how to use the numerical display for other Data Type.
20:13.4
20:21.2
This time we will use the data from Y output.
20:21.3
20:25.7
This is from the seven segment display
20:29.5
20:37.0
Practically BCD Data is very seldom used with HMI
20:37.1
20:48.5
since binary numbers and real numbers are used for data manipulations.
20:48.6
20:56.6
BCD Data can be used if there is existing BCD type devices
20:56.7
21:08.2
that is interfaced or converted to HMI display.
21:08.3
21:12.9
For example we select the BCD16 data type,
21:13.0
21:24.0
we will set the device as Y20
21:29.6
21:42.0
Click Shape to provide a frame for the numerical display
21:42.1
21:44.7
and set the plate color.
21:53.1
22:11.8
Supposing in the seven segment display we have a value of 125,
22:11.9
22:21.0
this value is monitored in the numerical display.
22:21.5
22:27.3
You will notice that the Y output has a value of 293.
22:27.4
22:32.2
This is the equivalent value of the binary digits.
22:38.0
22:50.0
For example we have a decimal value of 125.
22:50.1
22:59.6
In BCD conversion, each of the decimal digit has its equivalent value.
22:59.7
23:04.4
Decimal no. 1 is equal to 0001 in BCD.
23:06.9
23:11.4
Decimal no. 2 is equal to 0010 in BCD.
23:11.7
23:21.6
Decimal no. 5 is equal to 0101 in BCD.
23:21.7
23:27.3
Now if we combine the three BCD values into one,
23:27.4
23:33.8
it becomes a binary number 000100100101 which is equivalent to 293 in decimal.
23:38.0
23:43.4
That is the reason why the value of Y output is 293 and not 125.
24:30.0
24:46.9
Next we will make an example for Real Data Type numerical display.
24:50.2
24:53.9
The Display Format will also be Real type.
24:54.5
24:59.9
The device that we will use is D5 data register.
25:00.0
25:10.2
This program is a conversion from analog to digital value.
25:10.3
25:27.6
Data register D2 is from the input which is 0 to 10V converted to 0 to 4000 engineering units.
25:27.7
25:32.8
this will be converted from integer to floating type number.
25:32.9
25:36.0
If you notice it has decimal points in D3.
25:36.1
25:50.1
Then that value will be divided by 40 to scale the 0-4000 engineering units
25:50.2
25:57.9
will be scaled into 0 to 100°C.
25:58.0
26:01.1
This will be the scaled value.
26:38.5
26:41.7
As we can see we have two decimal points in the numerical display.
26:41.8
27:04.4
Supposing we have an engineering value of 2500, this will be equivalent to 62.5°C.
27:08.6
27:11.9
That is how we apply Real number in Data Format and Display Format.
27:12.0
27:20.5
The monitored value should be floating type.
27:22.4
27:33.5
In the PLC program the integer type should be converted to floating type.
27:42.0
27:57.0
If we want to add a unit, that is "°C", we need to put hash (#) sign,
27:57.1
28:29.5
we need to put hash (#) sign, that is three # signs,decimal point, two # signs and °C characters.
28:41.5
28:47.8
There we have now the °C unit for the numerical display.
28:49.8
28:54.2
For example our temperature input has changed,
28:56.3
29:09.5
For maximum of 4000 engineering units, the equivalent is 100°C.
29:24.0
29:39.3
That is for basic setup of numerical display using the data type Real and display format real.
29:39.4
29:54.6
If we use BIN format we can adjust the decimal point int the display format.
29:55.3
30:06.9
This is useful in PLCs that don't have floating number instruction.
30:07.0
30:18.4
Examples are FX1S and FX1N model PLCs.
30:24.7
30:31.1
What we can do is data manipulation so that we can
30:31.2
30:38.5
display the decimal points through HMI
30:38.6
30:45.0
although we don't have floating numbers in the PLC program.
30:45.1
30:59.0
Decimal point will be adjusted in the display format setting.
31:01.3
31:11.8
That is all for the basic setting on using the numerical display.
31:11.9
31:20.0
Watch out for more tutorials on Mitsubishi GOT HMI.
31:20.1
31:23.6
Thank you.