1
00:00:00,00 --> 00:00:05,000
Welcome to this new tutorial for Mitsubishi 
FX PLC.

2
00:00:05,100 --> 00:00:13,500
Our topic is about wiring of input devices 
to the FX Series PLC.

3
00:00:13,600 --> 00:00:19,000
PLC input signals could come from pushbuttons, 
on-off switch,

4
00:00:19,100 --> 00:00:22,500
key switch, limit switch, level or float 
switch, flow switch,

5
00:00:23,000 --> 00:00:28,500
pressure switch, temperature switch, photoelectric 
sensor or proximity sensors.

6
00:00:29,000 --> 00:00:33,900
Inputs from 1 to 8 are either normally open 
or

7
00:00:34,000 --> 00:00:36,500
normally closed voltage free contacts.

8
00:00:37,000 --> 00:00:42,000
Photoelectric or proximity sensors are usually 
transistor output

9
00:00:42,100 --> 00:00:48,000
which can be either NPN or PNP type transistor.

10
00:00:49,000 --> 00:00:54,000
Mitsubishi FX PLC input (X) terminals are 
common

11
00:00:54,100 --> 00:00:59,500
to sink or source  input of 24V DC internal 
power,

12
00:01:00,000 --> 00:01:05,000
except for earlier models like FX1S, FX1N 
and

13
00:01:05,100 --> 00:01:08,500
FX2N that has japanese specification.

14
00:01:09,000 --> 00:01:12,500
What is sink and source input?

15
00:01:12,600 --> 00:01:17,500
Sink and source refers to the direction of 
current flow

16
00:01:18,000 --> 00:01:23,000
into or out of the plc input terminals.

17
00:01:24,100 --> 00:01:27,500
Sink input is negative common.

18
00:01:27,600 --> 00:01:32,000
Sink input means a DC input signal with current 
flow

19
00:01:32,100 --> 00:01:34,500
from the input (X) terminal.

20
00:01:48,000 --> 00:01:53,500
From input going to the negative power supply 
(0V).

21
00:01:55,500 --> 00:01:58,400
When a sensor with a transistor output is 
connected,

22
00:01:58,500 --> 00:02:03,300
either proximity sensor or photoelectric 
sensor,

23
00:02:03,400 --> 00:02:07,500
NPN open collector transistor output can 
be used.

24
00:02:08,300 --> 00:02:16,500
It means if the PLC is connected as sink 
input

25
00:02:17,000 --> 00:02:24,400
NPN output sensors should be used.

26
00:02:24,500 --> 00:02:29,300

